Gate valve,resilient seat,Standard DIN3352,Face to face DIN3202 F4,PN10/16, DN40-DN1200
-
Design Standard:DIN3352
-
Face to face dimensions: DIN3202 F4
-
Flange:DIN2501,BS EN1092 PN10,PN16
-
Each valve be tested according to test standard: DIN3230
-
Work Temperature: 0-80°C
-
Working Pressure:PN10,PN16
-
Size:DN50-DN600
-
​
Materials:
-
Body: Ductile Iron(GGGG50)
-
Bonnet: Ductile Iron(GGGG50)
-
Wedge:Ductile iron coated by NBR or EPDM
-
Stem:2Cr13
-
Stem nut:Brass
-
Gland:Ductile iron or Brass
-
O ring:NBR
-
Gasket:NBR
-
Bonnet Bolts:Steel 8.8+Wax
-
Handwheel:Cast Iron(GG25) or Ductile iron(GGG50),or steel
Gate valve F4 Middle type Drawing
Gate valve F4 Middle type,Components and Materials
Gate valve F4 Middle type,Dimensions,DN50-DN300
Zhixin Valve Co. Ltd is one of professional manufacturer of ductile iron flanged resilient seated non rising stem gate valve DIN3352 F4 in China,high quality and competitive price.
Resilient seated gate valve of type F4 is designed to provide reliable shut-off or isolation for water and neutral fluid pipelines. Below are some key details about F4 resilient seat gate valves:
-
Design Standard: DIN3352 F4
-
Face-to-Face Dimension: Compliant with DIN3202-F4
-
Flange Standard: EN1092 PN16
-
Testing Standard: BS EN 5163, BS EN 1074-1 and 2 and BS EN12266.
-
Pressure Rating: Suitable for up to 16 Bar
-
Features: These robust gate valves have an elastomer-encapsulated wedge for superior sealing, ensuring effective shut-off.
How do I maintain a resilient seat gate valve?
To properly maintain a resilient seat gate valve, follow these steps:
1 Regular Inspection:
Check for any visible signs of wear, corrosion, or damage.Inspect the valve body, stem, and sealing surfaces.
Ensure that the valve operates smoothly without any sticking.
​
2 Lubrication:Apply a suitable valve lubricant to the stem threads and the gate wedge.Lubricate the stem nut and other moving parts as needed.
Follow the manufacturer’s recommendations for lubrication frequency.
​
3 Operate the Valve:Regularly open and close the valve to prevent it from becoming stuck.
Avoid excessive force during operation.If the valve has been unused for an extended period, exercise it to maintain flexibility.
​
4 Sealing Surface Cleaning:Remove any debris or buildup from the sealing surfaces.Use a soft brush or cloth to clean the gate and seat.Avoid abrasive materials that could damage the elastomer coating.
​
5Replace Damaged Parts:If you notice significant wear, cracks, or other damage, replace the affected parts promptly.Common replacement parts include the gate, stem, and seat.
Face to face for DIN3202/F4
The face-to-face dimensions for DIN 3202/F4,BS EN558 series 14, resilient seat gate valves are as follows (in millimeters):
-
DN 50: 150 mm
-
DN 65: 170 mm
-
DN 80: 180 mm
-
DN 100: 190 mm
-
DN 125: 200 mm
-
DN 150: 210 mm
-
DN 200: 230 mm
-
DN 250: 250 mm
-
DN 300: 270 mm
-
DN 350: 290 mm
-
DN 400: 310 mm
-
DN 450: 330 mm
-
DN 500: 350 mm
-
DN 600: 390 mm
-
DN700: 430mm
-
DN800: 470mm
-
DN900: 510mm
-
DN1000:550mm